My Account Log in

1 option

Electrical Arcing and Material Ignition Levels EATON Corporation, Innovation Center

SAE Technical Papers (1906-current) Available online

View online
Format:
Conference/Event
Author/Creator:
Hastings, Jerome K., author.
Conference Name:
SAE 2004 World Congress & Exhibition (2004-03-08 : Detroit, Michigan, United States)
Language:
English
Physical Description:
1 online resource
Place of Publication:
Warrendale, PA SAE International 2004
Summary:
Experimental data and analysis show the relationship between arcing watts, the time of the arc exposure and the degree to which common polymers experience damage. Arcing test apparatus for 125V DC and 48 volt DC are shown. Arc gap control allows 125-volts to mimic arcs in lower voltage systems. Arcing current waveforms depict the chaotic behavior of arcs and differences due to anode / cathode materials. Levels of degradation are defined and used for "Constant Damage Contours" for Vinyl, Carpeting and Sound insulation. The polymers were exposed to conditions of constant arcing watts for increasing times. Connecting the points of "first flame" establishes a "contour of constant damage". The data indicates that a "3 second flame free" limit is between 50 and 100 watts. 4000 watts of arcing takes 1/4 to second to cause burning. The influence of circuit resistance on the maximum arc power transfer is presented
Notes:
Vendor supplied data
Publisher Number:
2004-01-1565
Access Restriction:
Restricted for use by site license

The Penn Libraries is committed to describing library materials using current, accurate, and responsible language. If you discover outdated or inaccurate language, please fill out this feedback form to report it and suggest alternative language.

Find

Home Release notes

My Account

Shelf Request an item Bookmarks Fines and fees Settings

Guides

Using the Find catalog Using Articles+ Using your account